← FlexE Family
FlexEstack unit
FlexE / 05

FlexEstack

FlexEstack
Containerised Infrastructure Modules
Formerly CX Container Solution
Purpose-built

Containerised Infrastructure Modules for:

  • Generators and gensets
  • Control gear and switchrooms
  • Battery energy storage systems (BESS)
  • HV / MV switchgear and substations
  • Renewables and utility-scale equipment

DeliversA transportable, scalable environment for rapid global deployment.

FlexEstack is ISO-format infrastructure housing suitable for generators, control gear and other critical equipment. The container form factor unlocks standard global logistics — road, rail and sea — and a transport-rated base means the unit arrives ready to install without re-handling.

GeneratorsControl GearBESSHV/MV SubstationsRenewablesRemote SitesUtilities

Specifications

Indicative engineering data

Form factor
ISO 20 ft / 40 ft, high-cube optional
Base
Transport-rated integrated base, ISO corner castings
Ingress rating
IP54 standard
Handling
Crane, side-loader, rail and sea-freight rated
Access
Personnel door + optional equipment door
Design life
20+ years external
Lead time
Indicative 8–14 weeks

Technical Specifications

Detailed engineering parameters

Structural & Envelope

Form factor
ISO 20 ft / 40 ft (high-cube optional)
ISO dimensions
12 192 × 2 438 × 2 896 mm (40 ft HC reference)
Steel grade
S355 structural steel
Floor
Skid-proof knurled steel, press-formed and welded
Wall
Corrugated metal sheet; Class 0 soundproofing
Insulation
75 mm composite / PIR lining
U-value
0.25 W/m²K (typical)
Corrosion protection
C5-M marine coating; 240 µm DFT

Acoustic, Fire & Environment

Acoustic performance
Selectable 55 / 60 / 65 dB(A) @ 7 m
Ingress rating
IP54 standard
Ventilation
HVAC or filtered ventilation; motorised vents and baffles optional
Fire detection
Smoke and heat detection
Suppression
FM-200 gas suppression (optional)
Design life
20+ years external

Access & Internal Fit-out

Doors
Personnel door + optional equipment door; 3rd door with window optional
Safety
Emergency egress handles on internal doors
Fuel option
Internal bulk tanks — 800 L / 2 000 L
Electrical fit-out
Internal grids, distribution, lighting and small power (optional)

Logistics & Compliance

Lifting
ISO corner castings; crane and side-loader rated
Reference weight
Up to 25 t fully equipped
Transport
Standard global logistics — road, rail and sea
Certification
CSC Certified for international shipping
Lead time
Indicative 8–14 weeks

Scope

Standard, optional and what we never do

Standard

Included on every FlexEstack unit.

  • ISO-format steel enclosure with corner castings
  • Integrated transport-rated base
  • Weatherproof envelope, IP54
  • Personnel access door
  • Engineered cable and service entries
  • Lifting and lashing provisions

Optional extras

Specified per project, costed as add-ons.

  • HVAC or filtered ventilation package
  • Internal lighting, distribution and small power
  • Fire detection and suppression
  • Equipment-sized access door
  • Custom external livery / RAL

Exclusions

Out of scope — owned by other trades.

  • Equipment installed inside the module
  • Electrical terminations and cabling
  • Foundations and ground works (see FlexEfoot)
  • Network / fibre commissioning

WE NEVER TERMINATE POWER CABLING — THAT STAYS WITH THE ELECTRICAL CONTRACTOR / INTEGRATOR.